The i-power T-4101 series is a true online double-conversion UPS that can provide your critical equipment with reliable and stable sine wave power. It features significant advantages, including an output power factor of 0.8 and up to 98% AC-AC efficiency for greater energy savings.

It is a versatile, high quality, and cost-competitive UPS developed to handle a wide voltage range and inconsistent power conditions. The T-4101 series provides a safe power supply guaranteed for mission-critical applications such as computer equipment, telecommunication devices, precision instrument, network termination equipment, and more.

Product Highlights:

  • Wide Input Voltage Range; Single Phase 160Vac to 280Vac.
  • High Efficiency 98% under ECO Mode.
  • Battery low/over charged sensor to protect the charger.
  • Advanced SCR rectifier and IGBT inverter technology.
  • Surge current protection technology to manage sudden impact of 0% to 100% load immediately without transfer to bypass.
  • Front to rear ventilation design to reduce the MTTR rate of the UPS.
ModelOL1001T80600SOL1002T80600SOL1003T80800SOL1006T81600S OL1006T80800SOL1008T81600SOL1010T81600SOL1015T81600S
Capacity1KVA/0.8KW2KVA/1.6KW3KVA/2.4KW6KVA/4.8KW8KVA/6.4KW10KVA/8KW15KVA/12KW
Technical Specification
UPS StructureOnline Double Conversion
TopologyLow Frequency with Output Isolation Transformer
Overall Efficiency (AC-AC )> 85%
Noise(In 2 meters)< 50dB
Working Temp-10-40℃
Storage Temp-25 ~ 60℃(Without Batteries)
Humidity< 95%Non-Condensing
Safety StandardIEC62040
Parallel RedundancyAvailable
ProtectionsOverload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low
DC StartAvailable
Generator CompatibilityAvailable
DisplayLCD Display
IP RatingIP20
Cooling SystemIntelligent Speed Control Cooling Fan
Elevation<1000M,Without Derating
Rectifier Specification
Input Voltage200/220/230/240Vac Single Phase
Input Voltage Range160-280Vac
Input Frequency Range50Hz±5%
Soft-Start> 20 Seconds
Output Specification
Output Voltage200/220/230/240Vac
Output PF0.8
Output Voltage Regulation220Vac±1%( Static Load ),220Vac±2%(50~0% Sudden Change)
Output Freq50Hz±0.1%(BAT Mode)
Distortion<1%(Linear Full Load),< 3%(Non-Linear Full Load)
Frequency Tracking Range46-54Hz
Output WaveformPure Sine Wave
Overload> 125%: More than 1 Min;
> 150%: More than 300ms
> 125%: More than 10 Mins;
> 150%: More than 1 Min
Noise SuppressionEMI/RFI Wave Filter
Crest Ratio3∶1
Short-CircuitCircuit Auto Protection,Output Voltage/Current 0
Output AbnormalINV. Output Auto-Locked Protection
Bypass Specification
Static Bypass Transfer Time0ms
Static Bypass Range220Vac(-15~+15%)
Frequency Range±1Hz, ±2Hz,±3Hz Adjustable
Bypass - INV Transfer Time2ms
Frequency Tracking Speed0.5-2hz/s
Manual Maintenance BypassNoneAvailable
Alarm Specification
AlarmUtility Power Fault, BAT Voltage Low, Overload,UPS Fault
MuteAuto
Battery Specification
TypeSealed Lead Acid Maintenance Free
VDC72Vdc72Vdc96Vdc192Vdc / 96Vdc192Vdc192Vdc192Vdc
Charging Current5A - Standard 10A-Optional5A - Standard 10A-Optional5A - Standard 10A-Optional5A - Standard 10A-Optional5A - Standard 10A-Optional5A - Standard 10A-Optional5A - Standard 10A-Optional
BAT LowShutdown Protection
Communication Specification
Standard Communication PortRs232
OptionalSNMP/RS485/ Dry Contact
Remote SoftwareMulti-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control
Physical Parameters
Dimensions in mm(W×D×H)220×510×395220×610×475220×610×715
Net Weight (Kg)22.523.52944536370
Note:Specification are subject to change without further notice.