T-4102 3-In / 1-Out, without battery, 0.8 PF (6-30KVA)

The i-power T-4102 series is a true online double-conversion UPS that can provide your critical equipment with reliable and stable sine wave power. It features significant advantages, including an output power factor of 0.8 and up to 98% AC-AC efficiency for greater energy savings.
It is a versatile, high quality, and cost-competitive UPS developed to handle a wide voltage range and inconsistent power conditions. The T-4102 series provides a safe power supply guaranteed for mission-critical applications such as computer equipment, telecommunication devices, precision instrument, network termination equipment, and more.
Product Highlights:
- Wide Input Voltage Range; 3 Phase-In/1 Phase-out 380Vac ±25%.
- High Efficiency 98% under ECO Mode.
- Battery low/over charged sensor to protect the charger.
- Advanced SCR rectifier and IGBT inverter technology.
- Surge current protection technology to manage sudden impact of 0% to 100% load immediately without transfer to bypass.
- Front to rear ventilation design to reduce the MTTR rate of the UPS.
| Model | OL2006T83200S | OL2010T83200S | OL2015T83200S | OL2020T83200S | OL2030T83200S |
| Capacity | 6KVA/4.8KW | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW |
| Technical Specification | |||||
| UPS Structure | Online Double Conversion | ||||
| Topology | Low Frequency with Output Isolation Transformer | ||||
| Overall Efficiency (AC-AC ) | > 85% | ||||
| Noise(In 2 meters) | < 50dB | ||||
| Working Temp | -10-40℃ | ||||
| Storage Temp | -25 ~60℃(Without Batteries) | ||||
| Humidity | < 95%Non-Condensing | ||||
| Safety Standard | IEC62040 | ||||
| Parallel Redundancy | Available | ||||
| Protections | Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low | ||||
| DC Start | Available | ||||
| Generator Compatibility | Available | ||||
| Display | LCD Display | ||||
| Mute | Auto | ||||
| IP Rating | IP20 | ||||
| Cooling System | Intelligent Speed Control Cooling Fan | ||||
| Elevation | <1000M,Without Derated | ||||
| Rectifier Specification | |||||
| Input Voltage | 380Vac ±25% 3 Phase | ||||
| Input Voltage Range | 285-475Vac | ||||
| Input Frequency Range | 50Hz±5% | ||||
| Soft-Start | > 20 Seconds | ||||
| Output Specification | |||||
| Output Voltage | 200/220/230/240Vac | ||||
| Output PF | 0.8 | ||||
| Output Voltage Regulation | 220Vac±1% ( Static Load ), 220Vac±2% (50~0% Sudden Change) | ||||
| Output Freq | 50Hz±0.1%(BAT Mode) | ||||
| Distortion | <1%(Linear Full Load),< 3%(Non-Linear Full Load) | ||||
| Frequency Tracking Range | 46-54Hz | ||||
| Output Waveform | Pure Sine Wave | ||||
| Overload | > 125%: More than 1 Min; > 150%: More than 300ms | ||||
| Noise Suppression | EMI/RFI Wave Filter | ||||
| Crest Ratio | 3∶1 | ||||
| Short-Circuit | Circuit Auto Protection,Output Voltage/Current 0 | ||||
| Output Abnormal | INV. Output Auto-Locked Protection | ||||
| Bypass Specification | |||||
| Static Bypass Transfer Time | 0ms | ||||
| Static Bypass Range | 220Vac(-15~+15%) | ||||
| Frequency Range | ±1Hz, ±2Hz, ±3Hz | ||||
| Bypass - INV. Transfer Time | 2ms | ||||
| Frequency Tracking Speed | 0.5-2hz/s | ||||
| Manual Maintenance Bypass | None | Available | |||
| Alarm Specification | |||||
| Alarm | Utility Power Fault, BAT Voltage Low, Overload,UPS Fault | ||||
| Mute | Auto | ||||
| Battery Specification | |||||
| Type | Sealed Lead Acid Maintenance Free | ||||
| VDC | 336-384Vdc | ||||
| Charging Current | 5-10A (Adjustable) | ||||
| BAT Low | Shutdown Protection | ||||
| Communication And Specification | |||||
| Standard Communication Port | Rs232 | ||||
| Optional | SNMP/RS485/ Dry Contact | ||||
| Remote Software | Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control | ||||
| Physical Parameters | |||||
| Dimensions in mm(W×D×H) | 220×610×715 | 310×670×820 | |||
| Net Weight (Kg) | 67 | 74 | 99 | 117 | 125 |
| Note:Specification are subject to change without further notice. | |||||