T-4103 3-In / 3-Out, without battery, 0.9 PF (10-120KVA)
The i-power T-4103 series is a true online double-conversion UPS that can provide your critical equipment with reliable and stable power. It features significant advantages, including an output power factor of 0.9 and up to 90% AC-AC efficiency for greater energy savings.
The i-power T-4103 series offers the maximum available power, energy efficiency, and power performance for large data centres, telecommunication center, production line and related devices, requiring high power ratings and highly reliable power protection.
Product Highlights:
- Wide Input voltage range reduces the chance of battery drainage and extends battery life.
- Robust ECO Mode; Up to 98% efficiency with higher system reliability.
- Up to eight units can be paralleled for redundancy or expansion.
- Self-diagnosis and aging detection to minimize downtime risk.
- Advanced SCR rectifier and IGBT technology.
- AC-AC efficiency up to 90% for greater energy savings.
- High Load Compatibility and short-circuit protection.
Model | OL3010T93200S | OL3015T93200S | OL3020T93200S | OL3030T93200S | OL3040T93200S | OL3060T93200S | OL3080T93200S | OL3100T93200S | OL3120T93200S |
Capacity | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | 30KVA/27KW | 40KVA/32KW | 60KVA/54KW | 80KVA/72KW | 100KVA/90KW | 120KVA/108KW |
Technical Specification | |||||||||
UPS Structure | Online Double Conversion | ||||||||
Topology | Low Frequency with Output Isolation Transformer | ||||||||
Overall Efficiency (AC-AC) | 0.9 | ||||||||
Noise (In 2 Meters) | < 50-60dB | ||||||||
Working Temp. | 25 ~ 60℃ | ||||||||
Storage Temp. | 25 ~ 60℃ | ||||||||
Humidity | < 95%, Non-Condensing | ||||||||
National Standard | EN50091-1/IEC950 | ||||||||
International Standard | EN 50091-1/2; EN62040-1; EN62040-2 | ||||||||
Parallel Redundancy | Available upto 8 units | ||||||||
Protection | Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low | ||||||||
ECO | Available | ||||||||
EPO Function | Available | ||||||||
DC Start | Available | ||||||||
Generator Compatibility | Available | ||||||||
Display | LCD + LED | ||||||||
Mute | Auto | ||||||||
IP Rating | IP20 | ||||||||
Cooling System | Intelligent Speed Control Cooling Fan | ||||||||
Elevation | <1500M, Without Derated | ||||||||
Rectifier Specification | |||||||||
Input Voltage | 380Vac+N+W(3 phase + PE) | ||||||||
Input Voltage Range | 285-475Vac | ||||||||
Input Frequency Range | 45-65Hz | ||||||||
Input PF | 0.95( with input filter) | ||||||||
THDI | <5%(with optional accessories) | ||||||||
Dual Input Availability | Available(Optional accessories) | ||||||||
Input Mis Phase Protection | Misphase Alarm, UPS will not be started | ||||||||
Input Phase lost Protection | Phase Lost Alarm, UPS work on Bypass mode | ||||||||
Soft-Start | > 20 Seconds | ||||||||
Input Current | 23A | 31A | 39A | 54A | 70A | 100A | 125A | 160A | 192A |
Output Specification | |||||||||
Output Voltage | Line Voltage: 380×(1±1%)AC or Phase Voltage: 220×(1±1%)AC | ||||||||
Output PF | 0.8/0.9 (No lag) | ||||||||
Output Voltage Regulation | 380Vac±1%(Static Load);380Vac±2%(50-0% Sudden Change);380Vac±3%(100-0% Sudden Change) | ||||||||
Output Freq | ±8% at 50Hz: Online Mode tracking input and bypass freq.; ±0.1%: when input or bypass frequency is more than ±8% or under BAT Mode | ||||||||
THD | < 1%(Linear Full Load),< 3%(Non-Linear Full Load) | ||||||||
3 Phase Unbalanced | Allow 3 Phase 100% Unbalanced | ||||||||
Output Volt. Unbalanced | ≤1°(Balanced Load); ≤2°(50% Balanced Load) | ||||||||
Input/Output Phase Swift | ≤1°(Balanced Load); ≤2°(50% Balanced Load) | ||||||||
Frequency Tracking Range | 45-65Hz | ||||||||
Output Waveform | Pure Sine Wave | ||||||||
Overload | >125%: More than 10 mins; > 150%: More than 60s transfer to bypass | ||||||||
Crest Ratio | 3∶1 | ||||||||
Shor t-Circuit | Circuit Auto-Protection, Bypass Switch Tripping | ||||||||
Output Abnormal | INV. Output Auto-Locked Protection | ||||||||
Bypass Specification | |||||||||
Static Bypass Transfer Time | 0ms | ||||||||
Static Bypass Input Range | 380Vac(-15~+15%) | ||||||||
Frequency Range | 50/60Hz±1Hz, ±2Hz, ±3Hz Adjustable | ||||||||
Bypass - INV Transfer Time | 2ms | ||||||||
Frequency Tracking Speed | 0.5-2hz/s | ||||||||
Manual Maintenance Bypass | Available | ||||||||
Battery Specification | |||||||||
Charging Methods | DSP Controlled Charger: Equalized/Pulse Charge, Float Charge, Intelligent Battery Management | ||||||||
Type | Sealed Lead Acid Maintenance Free | ||||||||
VDC | 336-384VDC | ||||||||
Float Charge Voltage | 438Vdc | ||||||||
Charging Current | 5-10A | ||||||||
Abnormal Protections | BAT over-charged, Emergency charger shutdown protection or UPS shutdown protection | ||||||||
Communication Specification | |||||||||
Standard Communication Port | Rs232 | ||||||||
Optional | SNMP/RS485/ Dry Contact | ||||||||
Remote Software | Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control | ||||||||
Physical Parameters | |||||||||
Size in mm (W×H×D) | 475×990×700 | 550×1200×800 | 605×1350×800 | 800×1600×800 | |||||
Net Weight (Kg) | 210 | 223 | 230 | 280 | 330 | 450 | 550 | 630 | 750 |
Note:Specifications are subject to change without fur ther notice. |